For a protective environment room in a correctional treatment center, what governs the location of the supply outlets and exhaust inlets?The design must not compromise safety, security, and protection of staff, inmates, and property.Supply outlets must be opposite the head of the bed, and exhaust must be 3-24 inches above the floor behind the patient's head.Supply air must be delivered at or near the ceiling near the patient's bed, and exhaust registers must be 3-8 inches above the floor near the entrance.A minimum of 10 air changes per hour must be maintained.